Interactive reference diagram for Battery Energy Storage System power plant controllers. Showing the full signal chain from frequency measurement through droop response, PI control, rate/power limiting, and dispatch to PCS units. Click any block for tuning details and Fingrid SJV2024 requirements.
Reactive power capability and voltage control requirements for BESS connected to the Finnish grid. The PQ envelope, control modes, and response requirements differ significantly between Type B and Type C. Click any block in the diagram below for details.
| Requirement | Type B (0.1–10 MW) | Type C (10–75 MW) |
|---|---|---|
| Q range at Pmax | ±0.33 Pmax (cos φ ≥ 0.95) | ±0.33 Pmax (rectangular envelope) |
| PQ envelope shape | Triangular — Q narrows to 0 as P → 0 | Rectangular — full Q from ~0.2 Pmax upward |
| Q control modes | Fixed cos φ (primary) | Fixed cos φ, Q setpoint, Q(U), Q(P) |
| Q(U) voltage droop | Optional (DSO may request) | Mandatory — droop 2–5%, configurable |
| Remote Q dispatch | Not required | Mandatory via SCADA / EMS |
| Q step response | Not specified | ≤ 1 s to 90% of new setpoint |
| Voltage range | 0.90–1.10 p.u. at POC | 0.90–1.10 p.u. at POC |
| FRT Q priority | Not mandatory | Iq priority during fault (k-factor) |
| Grid-forming Q | Optional | Required for voltage source behaviour |